s7 1200 siemens 6ES7231-4HA30-0XB0 SIGNAL BOARD SB 1231, 1 AI

siemens simatic s7-1200, ANALOG INPUT SB 1231, 1 AI, +/- 10V DC (12 BIT RES.) OR 0 – 20 MA

Supply voltage
24 V DC Yes
Input current
from backplane bus 5 V DC, typ. 55 mA
Power losses
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 1; Current or voltage differential inputs
permissible input frequency for current input (destruction limit), max. ± 35 V
permissible input voltage for voltage input (destruction limit), max. 35 V
permissible input current for voltage input (destruction limit), max. 40 mA
permissible input current for current input (destruction limit), max. 40 mA
Cycle time (all channels) max. 156.25 µs; 400 Hz suppression
Input ranges
Voltage Yes; ±10 V, ±5 V, ±2.5 V
Current Yes; 0 to 20 mA
Thermocouple No
Resistance thermometer No
Resistance No
Input ranges (rated values), voltages
-10 V to +10 V Yes
Input resistance (-10 V to +10 V) ≥9 MOhm
-2.5 V to +2.5 V Yes
Input resistance (-2.5 V to +2.5 V) ≥9 MOhm
-5 V to +5 V Yes
Input resistance (-5 V to +5 V) ≥9 MOhm
Input ranges (rated values), currents
0 to 20 mA Yes
Analog outputs
Number of analog outputs 0
Analog value creation
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 11 bit; + sign
Integration time, parameterizable Yes
Interference voltage suppression for interference frequency f1 in Hz 40 dB, DC to 60 Hz
Smoothing of measured values
Parameterizable Yes
Step: None Yes
Step: low Yes
Step: Medium Yes
Step: High Yes
Errors/accuracies
Temperature error (relative to input area) 25 °C ±0.3% to 55 °C ±0.6% total measurement range
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Wire break No
Diagnostics indication LED
for status of the inputs Yes
for maintenance Yes
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
C-TICK Yes
FM approval Yes
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 660 hPa
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 795 hPa
Pollutant concentrations
SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 38 mm
Height 62 mm
Depth 21 mm
Weights
Weight, approx. 35 g

siemens industrial 6ES7223-1PL30-0XB0 DIGITAL I/O SM 1223

plc controllers 6ES7223-1PL30-0XB0  DIGITAL I/O SM 1223, 16DI/16DO
plc programsSIMATIC S7-1200, DIGITAL I/O SM 1223, 16DI / 16DO, 16DI DC 24 V, SINK/SOURCE, 16DO, RELAY 2A
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 180 mA
Digital inputs
from load voltage L+ (without load), max. 4 mA/input 11 mA/relay
Output voltage
Power supply to the transmitters
present Yes
Power losses
Power loss, typ. 10 W
Digital inputs
Number of digital inputs 16
In groups of 2
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max. 16
horizontal installation
up to 40 °C, max. 16
up to 50 °C, max. 16
vertical installation
up to 40 °C, max. 16
Input voltage
Rated value, DC 24 V
for signal “0″ 5 VDC at 1 mA
Input current
for signal “0″, max. (permissible quiescent current) 1 mA
for signal “1″, min. 2.5 mA
for signal “1″, typ. 4 mA; Typical
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable Yes; 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four
for interrupt inputs
Parameterizable Yes
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 300 m
Digital outputs
Number of digital outputs 16
In groups of 4
Product function / at the digital outputs / short-circuit protection No
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
with resistive load, max. 2 A
on lamp load, max. 30 W with DC, 200 W with AC
Output voltage
Rated value (DC) 5 to 30 V AC
Output current
for signal “1″ permissible range, max. 2 A
Output delay with resistive load
“0″ to “1″, max. 10 ms
“1″ to “0″, max. 10 ms
Aggregate current of outputs (per group)
horizontal installation
up to 50 °C, max. 8 A; Current per mass
Relay outputs
Number of relay outputs 16
Rated input voltage of relay coil L+ (DC) 24 V
Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000
Switching capacity of contacts
with inductive load, max. 2 A
on lamp load, max. 30 W with DC, 200 W with AC
with resistive load, max. 2 A
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostics indication LED
for status of the inputs Yes
For status of the outputs Yes
for maintenance Yes
Status indicator digital output (green) Yes
Status indicator digital input (green) Yes
Galvanic isolation
Galvanic isolation digital inputs
between the channels, in groups of 2
Galvanic isolation digital outputs
between the channels, in groups of 4
between the channels and the backplane bus 1500 V AC for 1 minute
Permissible potential difference
between different circuits 750 V AC for 1 minute
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
C-TICK Yes
FM approval Yes
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 660 hPa
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation
Permissible temperature change 5°C to 55°C, 3°C / minute
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 70 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 350 g