Posts tagged Siemens PLC

DIGITAL I/O module 6ES7223-1PH30-0XB0 SM 1223

plc siemens input output module 6ES7223-1PH30-0XB0 DIGITAL I/O SM 1223, 8DI/8DO
siemens s7 SIMATIC S7-1200, DIGITAL I/O SM 1223, 8DI / 8DO, 8DI DC 24 V, SINK/SOURCE, 8DO, RELAY 2A
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 145 mA
Digital inputs
from load voltage L+ (without load), max. 4 mA/input 11 mA/relay
Output voltage
Power supply to the transmitters
present Yes
Power losses
Power loss, typ. 5.5 W
Digital inputs
Number of digital inputs 8
In groups of 2
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max. 8
horizontal installation
up to 40 °C, max. 8
up to 50 °C, max. 8
vertical installation
up to 40 °C, max. 8
Input voltage
Rated value, DC 24 V
for signal “0″ 5 VDC at 1 mA
Input current
for signal “0″, max. (permissible quiescent current) 1 mA
for signal “1″, min. 2.5 mA
for signal “1″, typ. 4 mA; Typical
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable Yes; 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four
for interrupt inputs
Parameterizable Yes
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 300 m
Digital outputs
Number of digital outputs 8
In groups of 2
Product function / at the digital outputs / short-circuit protection No
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
with resistive load, max. 2 A
on lamp load, max. 30 W with DC, 200 W with AC
Output voltage
Rated value (DC) 5 to 30 V AC
Output current
for signal “1″ permissible range, max. 2 A
Output delay with resistive load
“0″ to “1″, max. 10 ms
“1″ to “0″, max. 10 ms
Aggregate current of outputs (per group)
horizontal installation
up to 50 °C, max. 10 A; Current per mass
Relay outputs
Number of relay outputs 8
Rated input voltage of relay coil L+ (DC) 24 V
Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000
Switching capacity of contacts
with inductive load, max. 2 A
on lamp load, max. 30 W with DC, 200 W with AC
with resistive load, max. 2 A
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostics indication LED
for status of the inputs Yes
For status of the outputs Yes
for maintenance Yes
Status indicator digital output (green) Yes
Status indicator digital input (green) Yes
Galvanic isolation
Galvanic isolation digital inputs
between the channels, in groups of 2
Galvanic isolation digital outputs
between the channels, in groups of 2
between the channels and the backplane bus 1500 V AC for 1 minute
Permissible potential difference
between different circuits 750 V AC for 1 minute
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
C-TICK Yes
FM approval Yes
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 660 hPa
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation
Permissible temperature change 5°C to 55°C, 3°C / minute
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 230 g

6ES7211-1BE31-0XB0 Siemens S7-1200 CPU 1211C

Siemens PLC 6ES7211-1BE31-0XB0  CPU 1211C, AC/DC/RELAY, 6DI/4DO/2AI ,Siemens S7 PLC,Siemens S7-1200 series,Simatic S7

General information
Engineering with
Programming package As of STEP 7 V11.0 SP2
Supply voltage
120 V AC Yes
230 V AC Yes
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Line frequency
permissible frequency range, lower limit 47 Hz
permissible frequency range, upper limit 63 Hz
Input current
Current consumption (rated value) 60 mA @ 120 VAC 30 mA @ 240 VAC
Inrush current, max. 20 A; at 264 V
Encoder supply
24 V encoder supply
24 V Permissible range: 20.4 to 28.8 V
Output current
Current output to backplane bus (DC 5 V), max. 750 mA; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 10 W
Memory
Usable memory for user data 30 kbyte
Work memory
integrated 30 kbyte
expandable No
Load memory
integrated 1 Mbyte
Backup
present Yes; (maintenance-free)
without battery Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction
for floating point arithmetic, typ. 2.5 µs; / instruction
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max. Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. 10 kbyte
Flag
Number, max. 4 kbyte; Size of bit memory address area
Address area
I/O address area
I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs
Process image
Inputs, adjustable 1 kbyte
Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 communication modules, 1 signal board
Time of day
Clock
Hardware clock (real-time clock) Yes
Deviation per day, max. +/- 60 s/month at 25 °C
Backup time 480 h; Typical
Digital inputs
Number of digital inputs 6; integrated
of which, inputs usable for technological functions 3; HSC (High Speed Counting)
integrated channels (DI) 6
m/p-reading Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max. 6
Input voltage
Rated value, DC 24 V
for signal “0″ 5 VDC at 1 mA
for signal “1″ 15 V DC at 2.5 mA
Input current
for signal “1″, typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in 4 groups
at “0″ to “1″, min. 0.2 ms
at “0″ to “1″, max. 12.8 ms
for interrupt inputs
Parameterizable Yes
for counter/technological functions
Parameterizable Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz
Cable length
Cable length, shielded, max. 500 m; 50 m for technological functions
Cable length unshielded, max. 300 m; For technological functions: No
Digital outputs
Number of digital outputs 4
integrated channels (DO) 4
Product function / at the digital outputs / short-circuit protection No
Switching capacity of the outputs
with resistive load, max. 2 A
on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
“0″ to “1″, max. 10 ms; max.
“1″ to “0″, max. 10 ms; max.
Switching frequency
of the pulse outputs, with resistive load, max. 1 Hz
Relay outputs
Max. number of relay outputs, integrated 4
Number of relay outputs 4
Number of operating cycles, max. mechanically 10 million, at rated load voltage 100,000
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Analog inputs
Integrated channels (AI) 2; 0 to 10 V
Number of analog inputs 2
Input ranges
Voltage Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) ≥100k ohms
Cable length
Cable length, shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 10 bit
Integration time, parameterizable Yes
Conversion time (per channel) 625 µs
Encoder
Connectable encoders
2-wire sensor Yes
1st interface
Type of interface PROFINET
Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
PROFINET IO Controller Yes
Communication functions
S7 communication
supported Yes
as server Yes
as client Yes
Open IE communication
TCP/IP Yes
ISO-on-TCP (RFC1006) Yes
UDP Yes
Web server
supported Yes
User-defined websites Yes
Test commissioning functions
Status/control
Status/control variable Yes
Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
Forcing Yes
Diagnostic buffer
present Yes
Integrated Functions
Number of counters 3
Counter frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Galvanic isolation
Galvanic isolation digital inputs
Galvanic isolation digital inputs 500 V AC for 1 minute
between the channels, in groups of 1
Galvanic isolation digital outputs
between the channels No
between the channels, in groups of 1
Permissible potential difference
between different circuits 500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes
Test voltage at air discharge 8 kV
Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
on the supply lines acc. to IEC 61000-4-4 Yes
Interference immunity on signal lines acc. to IEC 61000-4-4 Yes
Surge immunity
on the supply lines acc. to IEC 61000-4-5 Yes
Immunity against conducted interference induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes
Emission of radio interference acc. to EN 55 011
Emission of radio interferences acc. to EN 55 011 (limit class A) Yes; Group 1
Emission of radio interference acc. to EN 55 011 (limit class B) Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
C-TICK Yes
FM approval Yes
Marine approval Yes
Ambient conditions
Operating temperature
Min. -20 °C
max. 60 °C
horizontal installation, min. -20 °C
horizontal installation, max. 60 °C
vertical installation, min. -20 °C
vertical installation, max. 50 °C
Storage/transport temperature
Min. -40 °C
max. 70 °C
Air pressure
Operation, min. 795 hPa
Operation, max. 1080 hPa
Storage/transport, min. 660 hPa
Storage/transport, max. 1080 hPa
Relative humidity
Operation, max. 95 %; no condensation
Vibrations
Vibrations 2G wall mounting, 1G DIN rail
Operation, checked according to IEC 60068-2-6 Yes
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. -20 °C
max. 60 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 795 hPa
Permissible operating height -1000m to 2000m
Pollutant concentrations
SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Configuration
programming
Programming language
LAD Yes
FBD Yes
SCL Yes
Cycle time monitoring
adjustable Yes
Dimensions
Width 90 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 420 g
Status Aug 27, 2013
Product
Article Number (Market Facing Number) 6ES7211-1BE31-0XB0
Product Description SIMATIC S7-1200, CPU 1211C, COMPACT CPU, AC/DC/RELAY, ONBOARD I/O: 6 DI 24V DC; 4 DO RELAY 2A; 2 AI 0 – 10V DC, POWER SUPPLY: AC 85 – 264 V AC AT 47 – 63 HZ, PROGRAM/DATA MEMORY: 30 KB
Product family  CPU 1211C
Product Lifecycle (PLM) PM300:Active Product
Price data
Price Group 212
List Price
Customer Price
Surcharge for Raw Materials None
Metal Factor None
Delivery information
Export Control Regulations AL : N / ECCN : EAR99H
Delivery Time 1 Day/Days
Net Weight (kg) 0,403 Kg
Product Dimensions (W x L x H) Not available
Packaging Dimension 10.40 x 10.80 x 8.80
Package size unit of measure CM
Quantity Unit Piece
Packaging Quantity 1
Additional Product Information
EAN 6940408101395
UPC Not available
Commodity Code 85371091
LKZ_FDB/ CatalogID ST72
Product Group 4509
Country of origin China
RoHs Compliance RoHS compliant since: 15.06.2012
Product class A: Standard product which is a stock item could be returned within the returns guidelines/period.
Obligation Category for taking back electrical and electronic equipment after use No obligation to take back electrical and electronic equipment after use
Classifications
Version Classification
eClass 5.1 27-24-22-07
eClass 6 27-24-22-07
ETIM 5 EC000236
UNSPSC 8 43-20-15-03