Posts tagged s7-1200 modbus

siemens s71200 6ES7231-5QA30-0XB0 SIGNAL BOARD SB 1231 TC, 1 AI

programacion plc siemens SIMATIC S7-1200, ANALOG SB 1231 T, 1 X AI THERMOCOUPLE, TYPE J OR K

Supply voltage
24 V DC Yes
Input current
Current consumption, typ. 5 mA
from backplane bus 5 V DC, typ. 20 mA
Power losses
Power loss, typ. 0.5 W
Analog inputs
Number of analog inputs 1; Thermocouples
permissible input frequency for current input (destruction limit), max. ± 35 V
Technical unit for temperature measurement adjustable Degrees Celsius/degrees Fahrenheit
Input ranges
Thermocouple Yes; J, K; voltage range ±80 MV
Resistance thermometer No
Resistance Yes
Input ranges (rated values), voltages
-80 mV to +80 mV Yes
Input ranges (rated values), thermoelements
Type J Yes
Type K Yes
Thermocouple (TC)
Temperature compensation
Parameterizable No
Analog outputs
Number of analog outputs 0
Analog value creation
Measurement principle integrating
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 15 bit; + sign
Integration time, parameterizable No
Interference voltage suppression for interference frequency f1 in Hz 85 dB at 10 / 50 / 60 / 400 Hz
Analog value generation (in isochronous mode)
Smoothing of measured values
Parameterizable Yes
Errors/accuracies
Temperature error (relative to input area) 25 °C ±0.1 % to 55 °C ±0.2 % total measurement range
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode interference, min. 120 dB
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes; Can be read out
Wire break Yes
Diagnostics indication LED
for status of the inputs Yes
for maintenance Yes
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
C-TICK Yes
FM approval Yes
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 660 hPa
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 795 hPa
Pollutant concentrations
SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 38 mm
Height 62 mm
Depth 21 mm
Weights
Weight, approx. 35 g

s7 1200 siemens 6ES7221-1BF30-0XB0 SM 1221

simatic siemens 6ES7221-1BF30-0XB0 DIGITAL INPUT SM 1221, 8DI, 24V DC
plc module SIMATIC S7-1200, DIGITAL INPUT SM 1221, 8DI, 24V DC, SINK/SOURCE INPUT
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 105 mA
Digital inputs
from load voltage L+ (without load), max. 4 mA; per channel
Output voltage
Power supply to the transmitters
present Yes
Power losses
Power loss, typ. 1.5 W
Digital inputs
Number of digital inputs 8
In groups of 2
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max. 8
horizontal installation
up to 40 °C, max. 8
up to 50 °C, max. 8
vertical installation
up to 40 °C, max. 8
Input voltage
Rated value, DC 24 V
for signal “0″ 5 VDC at 1 mA
Input current
for signal “0″, max. (permissible quiescent current) 1 mA
for signal “1″, min. 2.5 mA
for signal “1″, typ. 4 mA; Typical
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable Yes; 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four
for interrupt inputs
Parameterizable Yes
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 300 m
Digital outputs
Number of digital outputs 0
Product function / at the digital outputs / short-circuit protection No
Interrupts/diagnostics/status information
Alarms
Alarms Yes
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostics indication LED
for status of the inputs Yes
for maintenance Yes
Status indicator digital input (green) Yes
Galvanic isolation
Galvanic isolation digital inputs
between the channels, in groups of 2
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
C-TICK Yes
FM approval Yes
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 660 hPa
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Permissible temperature range 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation
Permissible temperature change 5°C to 55°C, 3°C / minute
Connection method
required front connector Yes
Mechanics/material
Type of housing (front)
Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 170 g