plc scada SIMATIC S7-1200, DIGITAL OUTPUT SB 1222, 4DQ, 24VDC 200KHZ
Input current | |
from backplane bus 5 V DC, typ. | 50 mA |
Output voltage | |
Power supply to the transmitters | |
Supply current, max. | 4 mA; per channel |
Power losses | |
Power loss, typ. | 1 W |
Digital outputs | |
Number of digital outputs | 4; MOSFET, solid-state (current-sinking/current-sourcing) |
In groups of | 1 |
Product function / at the digital outputs / short-circuit protection | No |
Switching capacity of the outputs | |
with resistive load, max. | 0.1 A |
Load resistance range | |
upper limit | 10 Ω |
Output voltage | |
Rated value (DC) | 24 V |
for signal “0″, max. | 0.1 V; with 10 kOhm load |
for signal “1″, min. | 20 V |
Output current | |
for signal “1″ rated value | 0.1 A |
for signal “0″ residual current, max. | 10 µA |
Cable length | |
Cable length, shielded, max. | 50 m |
Interrupts/diagnostics/status information | |
Alarms | |
Alarms | Yes |
Diagnostic messages | |
Diagnostic functions | Yes |
Diagnostics indication LED | |
For status of the outputs | Yes |
Degree and class of protection | |
IP20 | Yes |
Standards, approvals, certificates | |
Marine approval according to Germanischer Lloyd | Yes |
Climatic and mechanical conditions for storage and transport | |
Climatic conditions for storage and transport | |
Free fall | |
Drop height, max. (in packaging) | 0.3 m; five times, in dispatch package |
Temperature | |
Permissible temperature range | -40 °C to +70 °C |
Air pressure acc. to IEC 60068-2-13 | |
Permissible air pressure | 1080 to 660 hPa |
Mechanical and climatic conditions during operation | |
Climatic conditions in operation | |
Temperature | |
Permissible temperature range | 0 °C to 55 °C horizontal installation 0 °C to 45 °C vertical installation |
Mechanics/material | |
Type of housing (front) | |
Plastic | Yes |
Dimensions | |
Width | 38 mm |
Height | 62 mm |
Depth | 21 mm |
Weights | |
Weight, approx. | 40 g |