General information |
Engineering with |
Programming package |
As of STEP 7 V11.0 SP2 |
Supply voltage |
120 V AC |
Yes |
230 V AC |
Yes |
permissible range, lower limit (AC) |
85 V |
permissible range, upper limit (AC) |
264 V |
Line frequency |
permissible frequency range, lower limit |
47 Hz |
permissible frequency range, upper limit |
63 Hz |
Input current |
Current consumption (rated value) |
100 mA @ 120 VAC 50 mA @ 240 VAC |
Inrush current, max. |
20 A; at 264 V |
Encoder supply |
24 V encoder supply |
24 V |
Permissible range: 20.4 to 28.8 V |
Output current |
Current output to backplane bus (DC 5 V), max. |
1600 mA; Max. 5 V DC for SM and CM |
Power losses |
Power loss, typ. |
14 W |
Memory |
Usable memory for user data |
75 kbyte |
Work memory |
integrated |
75 kbyte |
expandable |
No |
Load memory |
integrated |
4 Mbyte |
Backup |
present |
Yes; (maintenance-free) |
without battery |
Yes |
CPU processing times |
for bit operations, typ. |
0.085 µs; / instruction |
for word operations, typ. |
1.7 µs; / instruction |
for floating point arithmetic, typ. |
2.5 µs; / instruction |
CPU-blocks |
Number of blocks (total) |
DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
OB |
Number, max. |
Limited only by RAM for code |
Data areas and their retentivity |
retentive data area in total (incl. times, counters, flags), max. |
10 kbyte |
Flag |
Number, max. |
8 kbyte; Size of bit memory address area |
Address area |
I/O address area |
I/O address area, overall |
1024 bytes for inputs / 1024 bytes for outputs |
Process image |
Inputs, adjustable |
1 kbyte |
Outputs, adjustable |
1 kbyte |
Hardware configuration |
Number of modules per system, max. |
3 comm. modules, 1 signal board, 8 signal modules |
Time of day |
Clock |
Hardware clock (real-time clock) |
Yes |
Deviation per day, max. |
60 s/month at 25 °C |
Backup time |
480 h; Typical |
Digital inputs |
Number of digital inputs |
14; integrated |
of which, inputs usable for technological functions |
6; HSC (High Speed Counting) |
integrated channels (DI) |
14 |
m/p-reading |
Yes |
Number of simultaneously controllable inputs |
all mounting positions |
up to 40 °C, max. |
14 |
Input voltage |
Rated value, DC |
24 V |
for signal “0″ |
5 VDC at 1 mA |
for signal “1″ |
15 V DC at 2.5 mA |
Input current |
for signal “1″, typ. |
1 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
Parameterizable |
0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four |
at “0″ to “1″, min. |
0.2 ms |
at “0″ to “1″, max. |
12.8 ms |
for interrupt inputs |
Parameterizable |
Yes |
for counter/technological functions |
Parameterizable |
Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz |
Cable length |
Cable length, shielded, max. |
500 m; 50 m for technological functions |
Cable length unshielded, max. |
300 m; For technological functions: No |
Digital outputs |
Number of digital outputs |
10 |
integrated channels (DO) |
10 |
Product function / at the digital outputs / short-circuit protection |
No |
Switching capacity of the outputs |
with resistive load, max. |
2 A |
on lamp load, max. |
30 W with DC, 200 W with AC |
Output delay with resistive load |
“0″ to “1″, max. |
10 ms; max. |
“1″ to “0″, max. |
10 ms; max. |
Switching frequency |
of the pulse outputs, with resistive load, max. |
1 Hz |
Relay outputs |
Max. number of relay outputs, integrated |
10 |
Number of relay outputs |
10 |
Number of operating cycles, max. |
mechanically 10 million, at rated load voltage 100,000 |
Cable length |
Cable length, shielded, max. |
500 m |
Cable length unshielded, max. |
150 m |
Analog inputs |
Integrated channels (AI) |
2; 0 to 10 V |
Number of analog inputs |
2 |
Input ranges |
Voltage |
Yes |
Input ranges (rated values), voltages |
0 to +10 V |
Yes |
Input resistance (0 to 10 V) |
≥100k ohms |
Cable length |
Cable length, shielded, max. |
100 m; twisted and shielded |
Analog outputs |
Number of analog outputs |
0 |
Analog value creation |
Integrations and conversion time/ resolution per channel |
Resolution with overrange (bit including sign), max. |
10 bit |
Integration time, parameterizable |
Yes |
Conversion time (per channel) |
625 µs |
Encoder |
Connectable encoders |
2-wire sensor |
Yes |
1st interface |
Type of interface |
PROFINET |
Physics |
Ethernet |
Isolated |
Yes |
Automatic detection of transmission speed |
Yes |
Autonegotiation |
Yes |
Autocrossing |
Yes |
Functionality |
PROFINET IO Controller |
Yes |
Communication functions |
S7 communication |
supported |
Yes |
as server |
Yes |
as client |
Yes |
Open IE communication |
TCP/IP |
Yes |
ISO-on-TCP (RFC1006) |
Yes |
UDP |
Yes |
Web server |
supported |
Yes |
User-defined websites |
Yes |
Test commissioning functions |
Status/control |
Status/control variable |
Yes |
Variables |
Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
Forcing |
Forcing |
Yes |
Diagnostic buffer |
present |
Yes |
Integrated Functions |
Number of counters |
6 |
Counter frequency (counter) max. |
100 kHz |
Frequency meter |
Yes |
controlled positioning |
Yes |
PID controller |
Yes |
Number of alarm inputs |
4 |
Galvanic isolation |
Galvanic isolation digital inputs |
Galvanic isolation digital inputs |
500 V AC for 1 minute |
between the channels, in groups of |
1 |
Galvanic isolation digital outputs |
between the channels |
No |
between the channels, in groups of |
2 |
Permissible potential difference |
between different circuits |
500 V DC between 24 V DC and 5 V DC |
EMC |
Interference immunity against discharge of static electricity |
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 |
Yes |
Test voltage at air discharge |
8 kV |
Test voltage at contact discharge |
6 kV |
Interference immunity to cable-borne interference |
on the supply lines acc. to IEC 61000-4-4 |
Yes |
Interference immunity on signal lines acc. to IEC 61000-4-4 |
Yes |
Surge immunity |
on the supply lines acc. to IEC 61000-4-5 |
Yes |
Immunity against conducted interference induced by high-frequency fields |
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 |
Yes |
Emission of radio interference acc. to EN 55 011 |
Emission of radio interferences acc. to EN 55 011 (limit class A) |
Yes; Group 1 |
Emission of radio interference acc. to EN 55 011 (limit class B) |
Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
Degree and class of protection |
IP20 |
Yes |
Standards, approvals, certificates |
CE mark |
Yes |
CSA approval |
Yes |
UL approval |
Yes |
cULus |
Yes |
C-TICK |
Yes |
FM approval |
Yes |
Marine approval |
Yes |
Ambient conditions |
Operating temperature |
Min. |
-20 °C |
max. |
60 °C |
horizontal installation, min. |
-20 °C |
horizontal installation, max. |
60 °C |
vertical installation, min. |
-20 °C |
vertical installation, max. |
50 °C |
Storage/transport temperature |
Min. |
-40 °C |
max. |
70 °C |
Air pressure |
Operation, min. |
795 hPa |
Operation, max. |
1080 hPa |
Storage/transport, min. |
660 hPa |
Storage/transport, max. |
1080 hPa |
Relative humidity |
Operation, max. |
95 %; no condensation |
Vibrations |
Vibrations |
2G wall mounting, 1G DIN rail |
Operation, checked according to IEC 60068-2-6 |
Yes |
Shock test |
checked according to IEC 60068-2-27 |
Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Climatic and mechanical conditions for storage and transport |
Climatic conditions for storage and transport |
Free fall |
Drop height, max. (in packaging) |
0.3 m; five times, in dispatch package |
Temperature |
Permissible temperature range |
-40 °C to +70 °C |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
Min. |
-20 °C |
max. |
60 °C |
Air pressure acc. to IEC 60068-2-13 |
Permissible air pressure |
1080 to 795 hPa |
Permissible operating height |
-1000m to 2000m |
Pollutant concentrations |
SO2 at RH < 60% without condensation |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
Configuration |
programming |
Programming language |
LAD |
Yes |
FBD |
Yes |
SCL |
Yes |
Cycle time monitoring |
adjustable |
Yes |
Dimensions |
Width |
110 mm |
Height |
100 mm |
Depth |
75 mm |
Weights |
Weight, approx. |
455 g |