plc siemens s7-1200 6ES7215-1AG31-0XB0 CPU 1215C

s7 1200 siemens 6ES7215-1AG31-0XB0  CPU 1215C, DC/DC/DC, 14DI/10DO/2AI/2AO
simatic 1200 SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/DC, 2 PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO 24V DC 0.5A 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4 – 28.8 V DC, PROGRAM/DATA MEMORY: 100 KB
General information
Engineering with
Programming package As of STEP 7 V11.0 SP2
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 5 V
permissible range, upper limit (DC) 250 V
Input current
Current consumption (rated value) 500 mA; Typical
Current consumption, max. 1500 A; 24 V DC
Inrush current, max. 12 A; at 28.8 V DC
Output current
Current output to backplane bus (DC 5 V), max. 1600 mA; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 12 W
Memory
Usable memory for user data 100 kbyte
Work memory
integrated 100 kbyte
expandable No
Load memory
integrated 4 Mbyte
Backup
present Yes; (maintenance-free)
without battery Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction
for floating point arithmetic, typ. 2.5 µs; / instruction
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
Number, max. Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. 10 kbyte
Flag
Number, max. 8 kbyte; Size of bit memory address area
Address area
I/O address area
I/O address area, overall 1024 bytes for inputs / 1024 bytes for outputs
Process image
Inputs, adjustable 1 kbyte
Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
Hardware clock (real-time clock) Yes
Deviation per day, max. +/- 60 s/month at 25 °C
Backup time 480 h; Typical
Digital inputs
Number of digital inputs 14; integrated
of which, inputs usable for technological functions 6; HSC (High Speed Counting)
integrated channels (DI) 14
m/p-reading Yes
Number of simultaneously controllable inputs
all mounting positions
up to 40 °C, max. 14
Input voltage
Rated value, DC 24 V
for signal “0″ 5 VDC at 1 mA
for signal “1″ 15 V DC at 2.5 mA
Input current
for signal “1″, typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable Yes; 0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of four
at “0″ to “1″, min. 0.2 ms
at “0″ to “1″, max. 12.8 ms
for interrupt inputs
Parameterizable Yes
for counter/technological functions
Parameterizable Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz
Cable length
Cable length, shielded, max. 500 m; 50 m for technological functions
Cable length unshielded, max. 300 m; For technological functions: No
Digital outputs
Number of digital outputs 10
of which high-speed outputs 4; 100 kHz Pulse Train Output
integrated channels (DO) 10
Product function / at the digital outputs / short-circuit protection No
Limitation of inductive shutdown voltage to L+ (-48 V)
Switching capacity of the outputs
with resistive load, max. 0.5 A
on lamp load, max. 5 W
Output voltage
for signal “0″, max. 0.1 V; with 10 kOhm load
for signal “1″, min. 20 V
Output current
for signal “1″ rated value 0.5 A
for signal “0″ residual current, max. 0.1 mA
Output delay with resistive load
“0″ to “1″, max. 1 µs
“1″ to “0″, max. 5 µs
Switching frequency
of the pulse outputs, with resistive load, max. 100 kHz
Relay outputs
Max. number of relay outputs, integrated 0
Cable length
Cable length, shielded, max. 500 m
Cable length unshielded, max. 150 m
Analog inputs
Integrated channels (AI) 2; 0 to 10 V
Number of analog inputs 2
Input ranges
Voltage Yes
Input ranges (rated values), voltages
0 to +10 V Yes
Input resistance (0 to 10 V) ≥100k ohms
Cable length
Cable length, shielded, max. 100 m; twisted and shielded
Analog outputs
Integrated channels (AO) 2
Number of analog outputs 2
Cable length
Cable length, shielded, max. 100 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max. 10 bit
Integration time, parameterizable Yes
Conversion time (per channel) 625 µs
Encoder
Connectable encoders
2-wire sensor Yes
1st interface
Type of interface PROFINET
Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
PROFINET IO Controller Yes
2nd interface
Type of interface PROFINET
Physics Ethernet
Communication functions
S7 communication
supported Yes
as server Yes
as client Yes
Open IE communication
TCP/IP Yes
ISO-on-TCP (RFC1006) Yes
UDP Yes
Web server
supported Yes
User-defined websites Yes
Number of connections
overall 16; dynamically
Test commissioning functions
Status/control
Status/control variable Yes
Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
Forcing Yes
Diagnostic buffer
present Yes
Integrated Functions
Number of counters 6
Counter frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Number of pulse outputs 4
Galvanic isolation
Galvanic isolation digital inputs
Galvanic isolation digital inputs 500 V AC for 1 minute
between the channels, in groups of 1
Galvanic isolation digital outputs
Galvanic isolation digital outputs Yes
between the channels No
between the channels, in groups of 1
Permissible potential difference
between different circuits 500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes
Test voltage at air discharge 8 kV
Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
on the supply lines acc. to IEC 61000-4-4 Yes
Interference immunity on signal lines acc. to IEC 61000-4-4 Yes
Surge immunity
on the supply lines acc. to IEC 61000-4-5 Yes
Immunity against conducted interference induced by high-frequency fields
Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes
Emission of radio interference acc. to EN 55 011
Emission of radio interferences acc. to EN 55 011 (limit class A) Yes; Group 1
Emission of radio interference acc. to EN 55 011 (limit class B) Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
C-TICK Yes
FM approval Yes
Marine approval Yes
Ambient conditions
Operating temperature
Min. -20 °C
max. 60 °C
horizontal installation, min. -20 °C
horizontal installation, max. 60 °C
vertical installation, min. -20 °C
vertical installation, max. 50 °C
Storage/transport temperature
Min. -40 °C
max. 70 °C
Air pressure
Operation, min. 795 hPa
Operation, max. 1080 hPa
Storage/transport, min. 660 hPa
Storage/transport, max. 1080 hPa
Relative humidity
Operation, max. 95 %; no condensation
Vibrations
Vibrations 2G wall mounting, 1G DIN rail
Operation, checked according to IEC 60068-2-6 Yes
Shock test
checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
Permissible temperature range -40 °C to +70 °C
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
Min. -20 °C
max. 60 °C
Air pressure acc. to IEC 60068-2-13
Permissible air pressure 1080 to 795 hPa
Permissible operating height -1000 to 2000 m
Pollutant concentrations
SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Configuration
programming
Programming language
LAD Yes
FBD Yes
SCL Yes
Cycle time monitoring
adjustable Yes
Dimensions
Width 130 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 520 g